ETCR2000 Clamp Type Earth Resistance Tester is a major breakthrough in the traditional grounding resistance measurement technology, which is widely used in the grounding resistance measurement of electric power, telecommunications, meteorology, oil fields, construction and industrial electrical equipment.
The ETCR2000 Clamp Type Earth Resistance Tester does not need to disconnect the grounding lead and auxiliary electrode when measuring the loaned Ground system, which is safe, fast and easy to use.
ETCR2000 Clamp Type Earth Resistance Tester can measure the Ground fault that cannot be measured by traditional methods, and it can be applied to the situation that cannot be measured by traditional methods, because ETCR2000 Clamp Type Earth Resistance Tester measures the comprehensive value of the resistance of grounding body and the resistance of grounding lead.
In addition, the C - type clamp ground resistance meter can also measure the leakage current and neutral current of the ground system.
Power Supply | 6V DC(4 no.5 alkaline dry batteries) |
Operating Temperature | -10℃~55℃ |
Relative Humidity | 10%~90% |
LCD | 4-Digit LCD digital display, length and width 47×28.5mm |
Clamp Table Weight (Including Battery) | 1130g |
Clamp Table Size | Length 275mm, width 85mm, thickness 56mm |
Protection Level | Double insulation |
Structure Characteristics | Clamping mode |
Range Shift | Automatic |
External Magnetic Field | <40A/m |
External Electric Field | <1V/m |
Single Measurement Time | 1 SEC |
Resistance Measurement Frequency | >1KHz |
Highest Resolution Resistance Measurement | 0.001Ω |
Resistance Measurement Range | 0.01~1000Ω |
* Current Measurement Range | 0~30A(Type C) |
Measured Current Frequency | 50/60Hz |
Stored Measurement Data | 99units |
Setting Range of Resistance Alarm Critical Value | 1~199Ω |
* setting Range of Current Alarm Critical Value | 1~499mA(Type C) |
● Adopt advanced algorithm and digital integrated processing technology.
● Start the machine without waiting for self-check, and immediately enter the test.
● Breaking through the product bulky problem, more in line with the characteristics of handheld instrument.
● New appearance design, panel 6 key operation, performance through.
● The function of sound and light alarm and interference signal identification and indication are added.
● Measurement range increased to 0.01 Ω~1000, 99Ω groups of data will be stored, lower power consumption, the largest launch, working current is less than 50mA.